Explanation/Annotation:For continuous automated content control three (with, NO, SO2)
or any two (with and SO2; with and NO; SO2 and NO) from following components:
carbon oxides, nitric oxide or sulfur dioxide.
Detailed model description:Operating principle - optical-absorption.
method of sampling - compulsory.
measurement ranges:
for 0-5 0-15
SO2 0-1 and 0-2;. 0-30 and 0-60
NO 0-1 and 0-2
Îñí. Ïðèâåä. Inaccuracy, %
for and SO2 +-8
NO +-10
heating-up time, mine, not more 180
statements establishment, with, not more 300
Óíèôèöèð. Output signal, mitotic activity 0-5 or 4-20 under order
parameters measured environment:
temperature, degree. With +10-+500
moisture, ã/ì3, not more 240
pressure, kPa - 3, 9+ +4, 4
dust, ã/ì3, not more than 100
automatic calibration, ch 24+-0, 16 nils and sensibility
food, in 220
power consumption, VA, not more 550
overall dimensions, MM:
sampler 700õ135õ105
gas analyser box 712õ650õ1954
mass, kg, not more: on two component 260
on three êîìïîíåòà 275
lifetime, year, no less than 8 |